| Plan Review Notes For Permit 00081159 |
| Permit Number |
00081159 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED PER TONY MARCELLO 9-13-00 | | | | | | 1)TRUSS LAYOUT SHOWS GRC TRUSS TO THE | | | WALL WITH A CONNECTOR AND S2(A)INDICATES | | | THIS TRUSS TO BE ON TOP OF THE WALL. | | | PLEASE RECHECK THIS AREA FOR CONNECTORS, | | | UPLIFT LOADS AND FASTENERS. | | | | | | 2)DETAIL ON CONNECTION OF THE WINDOW AND | | | DOOR BUCKS TO MASONRY AS PER SEC.1606.2. | | | 6.2 | | | | | | 3)GRD TRUSS AS SHOWN ON CHAMBERS LAYOUT | | | AS LAYING ON THE BEARING WALL.SHEET S29A | | | SHOWS THIS TRUSS TO WALL. PLEASE CLARIFY | | | AND SHOW THE REQUIRED CONNECTORS. | | | | | | 4)TRUSS GRA ENGINEERING SHOWS UPLIFT OF | | | 1377# AND 1083# THE CONNECTOR A3 AS | | | SHOWN HAS AN UPLIFT OF 1080#. PLEASE | | | RECHECK. |
|