| Plan Review Notes For Permit 00081158 |
| Permit Number |
00081158 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO; | | | REVISED DRAWINGS REQUIRED BEFORE ROUGH | | | A/C INSPECTION | | | CORRECT; | | | 1.MASTER BATH DROP 10X6 CFM'S NOT CORECT | | | 2.6 INCH.DUCT TO MASTER CLOSET SIZE | | | DROP AND LIST CFM'S. | | | 3.4 INCH DUCT TO BATHROOM BY KITCHEN | | | SIZE DROP AND LIST CFM'S. | | | 4.MASTER TOILET ROOM EX-FAN CFM'S. | | | 5.NEED RETURN AIR FROM MASTER BEDROOM | | | IF OVER 300 CFM'S | | | 6.LIST SEER SEE A/C NOTES 5 E . |
|