Plan Review Notes
Plan Review Notes For Permit 00081084
Permit Number 00081084
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00.************* UNSAT *******************
 0
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 EQUIPMENT MAINS AND PANEL. PER 110-9 AND
 215-5.
  
 2)NOTE: PLEASE SEE 210-52-E FOR GFI REC
 INFRONT OF DWELLING.
  
 3)NOTE:PLEASE SEE 210-52D AND 210-11-C-3
 FOR THE REQ`D BATH(S) CIRCUIT(S). PLEASE
 LIST ON PANEL SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATON FOR
 REVIEW. PLANS WOULD HAVE PASSED WITH A
 PROVISO BUT WERE COMING BACK FOR OTHER
 COMMENTS. PLEASE TAKE CARE OF THE NOTES
 BEFORE RE-SUBMITTING. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
  