| 2001-02-01 00:00:00 | *************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT PANEL |
| | SCHEDULES ARE STILL NOT |
| | LABELED,,"A"B"C"ETC. |
| | |
| | 2)NOTE: PLEASE CLARIFY WHERE LOAD |
| | CALCULATIONS SHOW ALL CONTINUOUS LOADS |
| | AT 125%??. PLEASE CLARIFY THE NOTE ON |
| | PANELS |
| | "LOAD COMPUTERS@125%" ??? |
| | PLEASE SHOW LOAD CALCS PER 220. |
| | |
| | 3)NOTE: PLEASE NOTE TYPE-O FOR A/C |
| | RATINGS OF EQUIPMENT.NEEDS TO SHOW |
| | "AIC" |
| | ALSO PLEASE NOTE THAT ALL EQUIPMENT IS |
| | BEING SHOWN AT 100,000 AIC RATED! YET |
| | THEAVAILABLE FAULT CURRENT IS SHOWN |
| | LESSTHAN 10,000 AND 22,000 AVAILABLE? |
| | PLEASENOTE IF PLANS SHOW 100,000 THEN |
| | 100,000 RATED EQUIPMENT WILL HAVE TO BE |
| | INSATLLED. JUST A NOTE 100,000 RATED |
| | EQUIPMENT |
| | CAN BE 4,5,6 TIMES MORE IN PRICE THAN |
| | WHAT IS BEING NEEDED FROM CALCULATIONS |
| | ON E2.02. JUST A NOTE. |
| | |
| | 4)NOTE:PLEASE SHOW ALL BRANCH CIRCUIT |
| | `SFOR ALL, INCLUDING DETACHED BUILDING |
| | SHOWN ON E2.00. PLEASE CLARIFY WHERE |
| | POWER IS COMING FROM AND MEANS OF |
| | DISCONNECT PER 225-31. GROUNDING PER |
| | DETACHED BUILDING? |
| | |
| | 5)NOTE: PLEASE CLARIFY CIRCUITS FOR |
| | COMMON AREAS COMING FROM TENANT PANELS. |
| | WHERE IS HOUSE PANEL? WHY ARE CIRCUITS |
| | ON FIRST FLOOR COMING FROM PANEL/TENANT |
| | FROM THIRD FLOOR????? SECOND FLOOR ETC?? |
| | |
| | 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| | EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| | MECHANICAL CODE. |
| | |
| | 7)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| | SERVICE EQUIPMENT. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. PLEASE CALL IF THERE ARE |
| | ANYQUESTIONS OR CALL TO SET UP AN |
| | APPOINTMENT TO CLARIFY ANY ISSUES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |