2001-01-08 00:00:00DENIED;
  
 1.NOTE 20. CONDENSATE OVER 3 TONS MUST
 GO TO DRYWELL OR STORM SMC 304.8.3.
  
 2.NOTE 25. CLEANOUTS MUST BE NOT MORE
 THAN 80' FOR FOUR INCH. PIPE SPC 710.1
  
 3.PLUMBING RISER DIAGRAM NOT TO CODE;
 A.MAIN VENT SHOULD COMPLY WITH SPC
 918.
 B.VENT STACK SHOULD TIE INTO WASTE
 STACK 6" ABOVE HIGHEST FIXTURE AS
 MAIN VENT.
 C.WHERE DOES WASTE GO FROM W/C AND
 LAV. LEFT SIDE OF DIAGRAM ALL
 THREE FLOORS?
  
 4.(WATER RISER) COLD WATER MAIN GOES
 FROM 1 1/2 TO 1 1/4 BACK TO 1 1/2
 PLEASE RE-SIZE.
  
 5.SHOW HOT WATER RISER FROM FIRST FLOOR
 TO THIRD FLOOR.
  
 6.AIR CHAMBERS TO COMPLY WITH SPC
 607.8.3.
  
 7.SHOW SIZE AND TYPE OF WATER HEATER.
  
 8.DRINKING FOUNTAINS SHALL COMPLY WITH
 FACBC 4.1.3(10) (A) 415. PROVIISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBE BENDING OR STOOPING.
  
 9.HANDICAP STALLS (MENS ROOM) ALL THREE
 FLOORS MUST BE 66" WIDE FOR CLEAR
 FLOOR SPACE 36" FOR W/C AND 30" FOR
 LAVITORYS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377