| Plan Review Notes For Permit 00081069 |
| Permit Number |
00081069 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | | | | 1.NOTE 20. CONDENSATE OVER 3 TONS MUST | | | GO TO DRYWELL OR STORM SMC 304.8.3. | | | | | | 2.NOTE 25. CLEANOUTS MUST BE NOT MORE | | | THAN 80' FOR FOUR INCH. PIPE SPC 710.1 | | | | | | 3.PLUMBING RISER DIAGRAM NOT TO CODE; | | | A.MAIN VENT SHOULD COMPLY WITH SPC | | | 918. | | | B.VENT STACK SHOULD TIE INTO WASTE | | | STACK 6" ABOVE HIGHEST FIXTURE AS | | | MAIN VENT. | | | C.WHERE DOES WASTE GO FROM W/C AND | | | LAV. LEFT SIDE OF DIAGRAM ALL | | | THREE FLOORS? | | | | | | 4.(WATER RISER) COLD WATER MAIN GOES | | | FROM 1 1/2 TO 1 1/4 BACK TO 1 1/2 | | | PLEASE RE-SIZE. | | | | | | 5.SHOW HOT WATER RISER FROM FIRST FLOOR | | | TO THIRD FLOOR. | | | | | | 6.AIR CHAMBERS TO COMPLY WITH SPC | | | 607.8.3. | | | | | | 7.SHOW SIZE AND TYPE OF WATER HEATER. | | | | | | 8.DRINKING FOUNTAINS SHALL COMPLY WITH | | | FACBC 4.1.3(10) (A) 415. PROVIISIONS | | | SHALL BE MADE FOR PEOPLE WHO HAVE | | | TROUBE BENDING OR STOOPING. | | | | | | 9.HANDICAP STALLS (MENS ROOM) ALL THREE | | | FLOORS MUST BE 66" WIDE FOR CLEAR | | | FLOOR SPACE 36" FOR W/C AND 30" FOR | | | LAVITORYS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|