| Plan Review Notes For Permit 00081069 |
| Permit Number |
00081069 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-10 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: AS ASKED FOR ON PREVIOUS REVIEW, | | | PLEASE SHOW ALL BRANCH CIRCUIT#`S ON | | | PLANS AND CORRELATE WITH PANEL | | | SCHEDULES. | | | | | | 2)NOTE: PLEASE SHOW THE AIC RATINGS OF | | | EACH PIECE OF EQUIPMENT ON PLAN. FAULT | | | CURRENT IS SHOWN BUT JUST NEEDS TO HAVE | | | THE RATINGS SHOWN. | | | | | | 3)NOTE: PLEASE LABEL ALL PANELS IE. | | | "A","B", "C" ETC ETC | | | ALSO PLEASE SEE PLANS, PLANS SHOW 6 | | | PANELS AND ONLY 3 PANEL SCHEDULES WERE | | | SUBMITTED.? A,B,C SHOWN AND D,E,F IS | | | NOT SHOWN. ???? | | | | | | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | ATE 125%. (LIGHTING) IF LOADS ON PANEL | | | SCHEDULE ARE AT 125% ALREADY THEN PLEASE | | | INDICATE THIS. | | | | | | 5)NOTE: PLEASE SHOW OR CLARIFY THE | | | GROUNDING ELECTRODE CONDUCTOR, BLDG | | | STEEL, COLD WATER. PER 250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS PLEAS | | | E CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|