2001-01-10 00:00:00***************** UNSAT ****************
  
 1)NOTE: AS ASKED FOR ON PREVIOUS REVIEW,
 PLEASE SHOW ALL BRANCH CIRCUIT#`S ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULES.
  
 2)NOTE: PLEASE SHOW THE AIC RATINGS OF
 EACH PIECE OF EQUIPMENT ON PLAN. FAULT
 CURRENT IS SHOWN BUT JUST NEEDS TO HAVE
 THE RATINGS SHOWN.
  
 3)NOTE: PLEASE LABEL ALL PANELS IE.
 "A","B", "C" ETC ETC
 ALSO PLEASE SEE PLANS, PLANS SHOW 6
 PANELS AND ONLY 3 PANEL SCHEDULES WERE
 SUBMITTED.? A,B,C SHOWN AND D,E,F IS
 NOT SHOWN. ????
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 ATE 125%. (LIGHTING) IF LOADS ON PANEL
 SCHEDULE ARE AT 125% ALREADY THEN PLEASE
 INDICATE THIS.
  
 5)NOTE: PLEASE SHOW OR CLARIFY THE
 GROUNDING ELECTRODE CONDUCTOR, BLDG
 STEEL, COLD WATER. PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS PLEAS
 E CALL.
  