| 2001-01-08 00:00:00 | 1)ACCESSIBLE TOILET ROOMS WITHIN THE |
| | RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3 |
| | MIN.WIDTH SHALL BE 83"IF LAV.IS ADJACENT |
| | TO W.C.IF YOU DISAGREE CALL THE DEPT.OF |
| | COMMUNITY AFFAIRS AT 850-487-1824 FOR |
| | AN INTERPRETATION. |
| | |
| | 2)BREAK ROOM COUNTERS AND SINK SHALL |
| | COMPLY W/FACBC SEC.4.24.1-4.24.7. |
| | |
| | 3)DRINKING FOUNTAINS ARE REQD.ON EACH |
| | FLOOR PER TABLE 407 OF SPC.FOUNTAINS |
| | SHALL COMPLY W/FACBC SECS.4.1.3.(10)(A). |
| | 4.15.PROVISIONS SHALL BE MADE FOR PEOPLE |
| | WHO HAVE TROUBLE BENDING OR STOOPING. |
| | |
| | 4)FLOOR DRAINS ARE REQD.IN THE TOILET |
| | ROOMS PER SPC SEC.409.4.1.1.DRAINS SHALL |
| | BE EQUIPPED W/TRAP PRIMERS. |
| | |
| | 5)ALL EXPOSED PIPES AND SURFACES SHALL |
| | BE INSULATED PER FACBC SEC.4.19.4.(SEE |
| | SHT.A5). |
| | |
| | 6)SHT.A5-FIXTURE COUNT SHALL BE BASED ON |
| | THE 1994 STANDARD PLUMBING CODE,NOT 1997 |
| | |
| | 7)SUBMIT A WATER ISOMETRIC FOR REVIEW |
| | THAT COMPLIES W/SPC 1994 EDITION IN ALL |
| | RESPECTS. |
| | |
| | 8)SUBMIT A NEW SANITARY ISOMETRIC FOR |
| | REVIEW.THE ONE SUBMITTED HAS FAR TOO |
| | MANY VIOLATIONS TO LIST.COMPLY W/SPC. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |