| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE INFORMATION ON LOCATION AND | | | OPERATION OF HEAT WHEEL | | | 2. PROVIDE INFORMATION ON CONDENSATE | | | DRAIN INSTALLATION | | | 3. PROVIDE INFORMATION ON SEQUENCE OF | | | OPERATION ESP. O/A DAMPER. DAMPER SHALL | | | NOT REDUCE QUANTITY OF OUTSIDE AIR BELOW | | | ASHRAE 62-89 REQUIRED VALUES DURING | | | OCCUPIED TIMES | | | 4. FIRE DAMPERS NOT SHOWN AT ALL RATED | | | WALL PENETRATIONS. 1997 SMC 610.6 | | | REQUIRES LOCATION AND INSTALLATION | | | DETAILS ON THE BUILDING PLANS | | | 5.NO VENTILATION SHOWN FOR COMMON AREAS | | | 6. PROVIDE DETAILS ON SHAFTS SHOWING | | | COMPLIANCE WITH 1997 SMC 610.4 | | | 7. FAN SHUT DOWN BY DUCT SMOKE DETECTORS | | | REQUIRED PER 1997 SMC 406. | | | 8. NOTE: CONDENSING UNITS ARE TO BE | | | MOUNTED ON SOLID CONCRETE PADS MINIMUM | | | 3" ABOVE FINISHED GRADE. SERVICE ACCESS | | | AND ELECTRICAL ACCESS TO COMPLY WITH SMC | | | AND THE NATIONAL ELECTRIC CODE. |
|