2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE INFORMATION ON LOCATION AND
 OPERATION OF HEAT WHEEL
 2. PROVIDE INFORMATION ON CONDENSATE
 DRAIN INSTALLATION
 3. PROVIDE INFORMATION ON SEQUENCE OF
 OPERATION ESP. O/A DAMPER. DAMPER SHALL
 NOT REDUCE QUANTITY OF OUTSIDE AIR BELOW
 ASHRAE 62-89 REQUIRED VALUES DURING
 OCCUPIED TIMES
 4. FIRE DAMPERS NOT SHOWN AT ALL RATED
 WALL PENETRATIONS. 1997 SMC 610.6
 REQUIRES LOCATION AND INSTALLATION
 DETAILS ON THE BUILDING PLANS
 5.NO VENTILATION SHOWN FOR COMMON AREAS
 6. PROVIDE DETAILS ON SHAFTS SHOWING
 COMPLIANCE WITH 1997 SMC 610.4
 7. FAN SHUT DOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 1997 SMC 406.
 8. NOTE: CONDENSING UNITS ARE TO BE
 MOUNTED ON SOLID CONCRETE PADS MINIMUM
 3" ABOVE FINISHED GRADE. SERVICE ACCESS
 AND ELECTRICAL ACCESS TO COMPLY WITH SMC
 AND THE NATIONAL ELECTRIC CODE.