| Plan Review Notes For Permit 00081069 |
| Permit Number |
00081069 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. THE CODE RESEARCH BOX | | | INDICATES FIRE SPRINKLERS ARE PRESENT | | | IN THE CORRIDORS ONLY. | | | 2) NO FIRE ALARM SYSTEM SHOWN ON | | | DRAWINGS. PLEASE BE ADVISED THAT SINCE | | | THE BUILDING IS THREE STORIES HIGH, A | | | FIRE ALARM SYSTEM IS REQUIRED. PLEASE | | | NOTE THAT THE EXISTING FIRE SPRINKLER | | | SYSTEM SHOULD BE SUPERVISED IN | | | ACCORDANCE WITH BUILDING AND FIRE CODE | | | REQUIREMENTS. | | | 3) ALL STORAGE, EQUIPMENT, AND | | | MECHANICAL ROOMS IF NOT FIRE SPRINKLER | | | PROTECTED TO BE AT LEAST ONE HOUR FIRE | | | RATED WITH C LABELED FIRE DOORS WITH | | | SELF-CLOSING DEVICES. | | | 4) PLEASE PROVIDE MORE INFORMATION ON | | | SIX INCH STEP NEAR STAIR B. |
|