Plan Review Notes
Plan Review Notes For Permit 00081069
Permit Number 00081069
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. THE CODE RESEARCH BOX
 INDICATES FIRE SPRINKLERS ARE PRESENT
 IN THE CORRIDORS ONLY.
 2) NO FIRE ALARM SYSTEM SHOWN ON
 DRAWINGS. PLEASE BE ADVISED THAT SINCE
 THE BUILDING IS THREE STORIES HIGH, A
 FIRE ALARM SYSTEM IS REQUIRED. PLEASE
 NOTE THAT THE EXISTING FIRE SPRINKLER
 SYSTEM SHOULD BE SUPERVISED IN
 ACCORDANCE WITH BUILDING AND FIRE CODE
 REQUIREMENTS.
 3) ALL STORAGE, EQUIPMENT, AND
 MECHANICAL ROOMS IF NOT FIRE SPRINKLER
 PROTECTED TO BE AT LEAST ONE HOUR FIRE
 RATED WITH C LABELED FIRE DOORS WITH
 SELF-CLOSING DEVICES.
 4) PLEASE PROVIDE MORE INFORMATION ON
 SIX INCH STEP NEAR STAIR B.