| Plan Review Notes For Permit 00081069 |
| Permit Number |
00081069 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS SHOWING ALL | | | BRANCH CIRCUIT #`S AND CORRELATE WITH | | | PANEL SCHEDULES | | | | | | 2)NOTE: PLEASE SHOW DETAIL ON PANELS | | | BEING INSTALLED. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED.MAINS/ | | | PANELS/BREAKERS. 110-9 AND 215-5 | | | | | | 4)NOTE:PLEASE SEE BOTTOM OF PANEL/LOAD | | | SCHEDULE SHOWN. YOU SHOW SERVICE TO BE | | | FURNISHED AS 400AMP. IS THIS GOING TO BE | | | BYTWO SEPARATE SERVICES?PLEASE SEE | | | NEC FOR TWO SERVICES SERVING ONE SPACE. | | | | | | 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. LIGHTING ETC. | | | | | | 6)NOTE: PLEASE SHOW WIRE SIZES,BRKR SIZE | | | -S ETC FOR PANEL SCHEDULES. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|