| Plan Review Notes For Permit 00081067 |
| Permit Number |
00081067 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-19 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | RISER DIAGRAM. WHERE IS THIS SERVICE | | | LOCATED? WHAT IS THE FEED FROM PANEL | | | SHOWN AS 1 1/2 CONDUIT W/3-#2`S?? | | | PLEASE CLARIFY EQUIPMENT GROUND BETWEEN | | | MAIN AND PANEL. | | | | | | 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANSAND CORRELATE WITH | | | SUBMITTED PANEL SCHEDULE. | | | | | | 3)NOTE: PLEASE SHOW A/C UNIT LOCATIONS | | | WITH REQ`D DISCONNECT. | | | | | | 4)NOTE: PLEASE NOTE THAT NEW BLDG. STEEL | | | NEEDS TO BE SHOWN AS PART OF THE | | | GROUNDING ELECTRODE SYSTEM. PER 250-50 | | | | | | PLEASE SUBMTI THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|