| Plan Review Notes For Permit 00081051 |
| Permit Number |
00081051 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO CUT SHEETS PROVIDED FOR SMOKE | | | AND HEAT DETECTORS PLANNED FOR | | | INSTALLATION. | | | 2) NO HORN STROBES SHOWN ON PLAN. PLEASE | | | BE ADVISED THAT THE 1997 STANDARD | | | BUILDING CODE SECTION 903.8.3 REQUIRES | | | THAT WHEN THE FIRE SPRINKLER SYSTEM IS | | | ACTIVATED, THE BUILDING FIRE ALARM | | | SYSTEM IS TO SOUND. HOW IS THIS | | | REQUIREMENT GOING TO BE ACCOMPLISHED. | | | 3) NO INDICATION OF THE FIRE ALARM | | | SYSTEM BEING MONITORED. THE FIRE | | | SPRINKLER SYSTEM IS TO BE SUPERVISED BY | | | BUILDING AND FIRE CODES. |
|