| Plan Review Notes For Permit 00081031 |
| Permit Number |
00081031 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. | | | 2) INTERIOR FINISH ON WALLS AND CEILINGS | | | SHALL BE CLASS A OR B. PLEASE NOTE | | | THIS ON PLANS. | | | 3) EXITING THROUGH STOCKROOM PERMITTED | | | IF THE FOLLOWING CONDITIONS ARE PRESENT, | | | DOOR LEADING TO STOCKROOM CANNOT BE | | | LOCKED, AN AISLE OF AT LEAST 44" WIDE | | | SHALL BE PROVIDED, THIS 44" AISLE IS | | | TO BE MAINTAINED, AND NO MORE THAN | | | 50 PERCENT OF EXIT ACESS CAN BE THROUGH | | | STOCKROOM. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 5) PLEASE PROVIDE FIRE ALARM PLANS FOR | | | FIRE ALARM DEVICES SHOWN ON PLANS. PULL | | | STATIONS ARE NOT NECESSARY IN TENANT | | | SPACES. | | | 6) ADDITIONAL EXIT SIGN IS REQUIRED AT | | | REAR EXIT DOOR. |
|