Plan Review Notes
Plan Review Notes For Permit 00081031
Permit Number 00081031
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE 220-3-B-7/220-12-A
 FOR THE REQ`D LOAD CALCULATIONS FOR
 SHOW WINDOWS.
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.(LIGHTING)
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS
 215-5
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 AND CONNECTION FOR GROUNDING. TRANSFORM-
 -ER. ETC.
  
 5)NOTE: PLEASE SEE LOADS FOR LIGHTING
 CIRCUITS #`S 3,5. LOAD SHOWN IS ABOVE
 80% FOR BREAKERS. PLEASE CORRECT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.