| Plan Review Notes For Permit 00081031 |
| Permit Number |
00081031 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE 220-3-B-7/220-12-A | | | FOR THE REQ`D LOAD CALCULATIONS FOR | | | SHOW WINDOWS. | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%.(LIGHTING) | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | 215-5 | | | | | | 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | AND CONNECTION FOR GROUNDING. TRANSFORM- | | | -ER. ETC. | | | | | | 5)NOTE: PLEASE SEE LOADS FOR LIGHTING | | | CIRCUITS #`S 3,5. LOAD SHOWN IS ABOVE | | | 80% FOR BREAKERS. PLEASE CORRECT. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|