2001-01-08 00:00:001)SHOW CLEAR FLOOR SPACE FOR DRINKING
 FOUNTAINS AND BREAKROOM SINK ON THE PLAN
 FIXTURES CANNOT OBSTRUCT CLEAR ACCESS TO
 OTHER FIXTURES.CLEAR FLOOR SPACES FOR
 FIXTURES MAY OVERLAP.4.15.5,4.19.3.
  
 2)MIN.SIZE OF HEATER PAN DRAIN SHALL BE
 1"PER SPC SEC.507.8.2.
  
 3)BENCH IN H.C.FITTING ROOM SHALL COMPLY
 W/FACBC SEC.4.35.4.MIRROR SHALL COMPLY
 W/SEC.4.35.5.
  
 4)BREAKROOM SINK SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.