| Plan Review Notes For Permit 00081025 |
| Permit Number |
00081025 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG TRAVEL DISTANCE NOTED ON PLANS. | | | SHOULD READ 150 FEET INSTEAD OF 250 | | | FEET BECAUSE THE SPACE IS FIRE SPRINKLER | | | PROTECTED. CODE NFPA 101, 1985 EDITION. | | | 2) AN ADDITIONAL EXIT SIGN IS NEEDED TO | | | DIRECT PERSONS TO CORRIDOR 006. | | | 3) PLEASE INDICATE EMERGENCY LIGHT | | | FIXTURES IN SALES AREA. | | | 4) ADDITIONAL FIRE ALARM DEVICES ARE | | | NEEDED WITHIN TENANT SPACE. | | | 5) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF AN AISLE OF AT LEAST 44" WIDE | | | IS PRESENT, THIS 44" AISLE MUST BE | | | MAINTAINED. |
|