Plan Review Notes
Plan Review Notes For Permit 00081025
Permit Number 00081025
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) WRONG TRAVEL DISTANCE NOTED ON PLANS.
 SHOULD READ 150 FEET INSTEAD OF 250
 FEET BECAUSE THE SPACE IS FIRE SPRINKLER
 PROTECTED. CODE NFPA 101, 1985 EDITION.
 2) AN ADDITIONAL EXIT SIGN IS NEEDED TO
 DIRECT PERSONS TO CORRIDOR 006.
 3) PLEASE INDICATE EMERGENCY LIGHT
 FIXTURES IN SALES AREA.
 4) ADDITIONAL FIRE ALARM DEVICES ARE
 NEEDED WITHIN TENANT SPACE.
 5) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF AN AISLE OF AT LEAST 44" WIDE
 IS PRESENT, THIS 44" AISLE MUST BE
 MAINTAINED.