Plan Review Notes
Plan Review Notes For Permit 00081025
Permit Number 00081025
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SHOW LOAD CALCULATION/S/
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
  
 2)NOTE: PLEASE SEE 220-3-B-7/ 220-12-A
 FOR SHOW WINDOW REQ`MENTS.
  
 3)NOTE: PLEASE SEE 220-12-B FOR TRACK
 LIGHTING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372