| Plan Review Notes For Permit 00080956 |
| Permit Number |
00080956 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM ADDITIONS SHALL BE | | | CLASS A, STYLE D WIRED OR BE ADDRESSABLE | | | 2) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | | TO BE AUDIBLE THROUGHOUT SPACE. | | | 3) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM ANY AIR | | | CONDITIONER DIFFUSERS. | | | 4) SYSTEM AFTER INSTALLATION TO BE | | | TESTED WITH FIRE RESCUE REPRESENTATIVES. | | | 5) FIRE ALARM EQUIPMENT INSTALLED ON THE | | | NINTH FLOOR IS TO BE CONNECTED TO THE | | | BASE BUILDING FIRE ALARM SYSTEM. |
|