| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* PROVISO ****************** | | | | | | 1)NOTE: PLEASE PROVIDE PLANS WITH ALL | | | BRANCH CIRCUIT #`S ON LAYOUT AND | | | PLEASE CORRELATE WITH PANEL SCHEDULE. | | | | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATION | | | FOR PANEL SHOWING ALL CONTINUOUS LOADS | | | AT 125%. YOU ARE ONLY TWO CIRCUITS ON | | | PANEL SCHEDULE? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|