| Plan Review Notes For Permit 00080936 |
| Permit Number |
00080936 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-04-05 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE ORIGINAL | | | PLAN WAS SUBMITTED AGAIN WITH | | | HANDWRITTEN CHANGES W/OUT ENGINEER OF | | | RECORD SIGING EACH CHANGE. ALSO, THE | | | COPY OF PLAN IS VERY UNCLEAR. PLEASE | | | NOTE UNDER F.S. | | | F.A.C, COUNTY AND CITYWIDE | | | ADMINISTRATIVE CODE. 104.2, 104.2.1, | | | 471.025 PLANS ARE TO BE CLEAR AND | | | LEGIABLE.PLEASE HAVE ELECTRICAL PART | | | OF PLAN RE-DRAWN . | | | | | | | | | 2)NOTE: PLEASE NOTE THERE ARE NOT ENOUGH | | | CONDUCTORS SHOWN COMING FROM MAIN PANEL | | | AT HOUSE. PLANS SHOW 2-6`S AND 1-#8. | | | WHERE IS NEUTRAL? OR IS #8 NEUTRAL? IF | | | SO THEN WHERE IS EQUIPMENT GROUNDING | | | CONDUCTOR? | | | | | | 3)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | BATH. 210-52D ,#12, 20A. | | | | | | 4)NOTE: PLEASE NOTE THAT PLANS SHOW THAT | | | THERE IS NO ADDED LOAD ? HOW IS THIS | | | POSSIBLE? | | | | | | AS ON PREVIOUS NOTES, PLEASE CALL IF THE | | | RE ARE ANY QUESTIONS, OR CLARIFICATION | | | NEEDED. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|