2001-04-05 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE ORIGINAL
 PLAN WAS SUBMITTED AGAIN WITH
 HANDWRITTEN CHANGES W/OUT ENGINEER OF
 RECORD SIGING EACH CHANGE. ALSO, THE
 COPY OF PLAN IS VERY UNCLEAR. PLEASE
 NOTE UNDER F.S.
 F.A.C, COUNTY AND CITYWIDE
 ADMINISTRATIVE CODE. 104.2, 104.2.1,
 471.025 PLANS ARE TO BE CLEAR AND
 LEGIABLE.PLEASE HAVE ELECTRICAL PART
 OF PLAN RE-DRAWN .
  
  
 2)NOTE: PLEASE NOTE THERE ARE NOT ENOUGH
 CONDUCTORS SHOWN COMING FROM MAIN PANEL
 AT HOUSE. PLANS SHOW 2-6`S AND 1-#8.
 WHERE IS NEUTRAL? OR IS #8 NEUTRAL? IF
 SO THEN WHERE IS EQUIPMENT GROUNDING
 CONDUCTOR?
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 BATH. 210-52D ,#12, 20A.
  
 4)NOTE: PLEASE NOTE THAT PLANS SHOW THAT
 THERE IS NO ADDED LOAD ? HOW IS THIS
 POSSIBLE?
  
 AS ON PREVIOUS NOTES, PLEASE CALL IF THE
 RE ARE ANY QUESTIONS, OR CLARIFICATION
 NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372