| 2001-03-20 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASENOTE THAT PER F.A.C. | | | ALL PLANS THAT ARE SIGNED AND SEALED BY | | | AN ARCH/ENGINEER NEED TO HAVE ALL | | | CHANGES DONE BY THAT PERSONOF RECORD. | | | | | | 2)NOTE: PLEASE NOTE PLANS ARE TO BE RE- | | | DONE TO MEET ALL ORIGINAL NOTES. | | | | | | 3)NOTE: PLEASE NOTE THAT TWO COPIES ARE | | | TO BE SUBMITTED FOR REVIEW. ONE COMES | | | BACK FOR YOUR RECORD ON THE JOB AND THE | | | OTHER IS FOR OUR RECORD. | | | | | | 4)NOTE: PLEASE CLARIFY PLANS SHOWING | | | 3-2/0`S GOING TO A 60A MAIN. PLEASE | | | CLARIFY HOW 2/0 WIRE IS GOING TO FIT | | | INTO A 60A MAIN.?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|