Plan Review Notes
Plan Review Notes For Permit 00080936
Permit Number 00080936
Review Stop E
Sequence Number 3
Notes
Date Text
2001-03-20 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASENOTE THAT PER F.A.C.
 ALL PLANS THAT ARE SIGNED AND SEALED BY
 AN ARCH/ENGINEER NEED TO HAVE ALL
 CHANGES DONE BY THAT PERSONOF RECORD.
  
 2)NOTE: PLEASE NOTE PLANS ARE TO BE RE-
 DONE TO MEET ALL ORIGINAL NOTES.
  
 3)NOTE: PLEASE NOTE THAT TWO COPIES ARE
 TO BE SUBMITTED FOR REVIEW. ONE COMES
 BACK FOR YOUR RECORD ON THE JOB AND THE
 OTHER IS FOR OUR RECORD.
  
 4)NOTE: PLEASE CLARIFY PLANS SHOWING
 3-2/0`S GOING TO A 60A MAIN. PLEASE
 CLARIFY HOW 2/0 WIRE IS GOING TO FIT
 INTO A 60A MAIN.??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372