| 2001-01-08 00:00:00 | ************* REVISION REQUESTED ******* | | | | | | 1)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | PANEL FOR GARAGE. MAIN BRKR? A MAIN | | | MEANS OF DISCONNECT IS REQ`D. | | | | | | 2)NOTE: PLEASE SHOW GROUNDING PER NEC | | | FOR DETACHED GARAGE. COLD WATER,GRND ROD | | | | | | 3)NOTE: PLEASE SEE REQ`MENTS FOR SD`S | | | INSIDE SLEEPING ROOMS! NFPA-72 2-2.1.1.1 | | | | | | 4)NOTE: PLEASE PROVIDE A GFI REC OUTSIDE | | | PER 210-52E | | | | | | THE FOLLOWING ARE NOTES TO QUESTION | | | ANY OTHER ISSUES THAT MAY ARISE. | | | IS THERE GOING TO BE CATV OR TELEPHONE | | | OUTLETS INSTALLED?? | | | WHERE IS THE HOT WATER COMING FROM? | | | PLEASE CLARIFY! | | | IS THERE GOING TO BE CENTRAL A/C OR IS | | | THERE GOING TO BE A WINDOW UNIT? | | | PLEASE PROVIDE CLARIFICATION ON THE | | | ABOVE INFORMATION. | | | | | | ALSO PLEASE NOTE THAT PROVISIONS FOR | | | KITCHEN COOKING EQUIPMENT WILL NOT BE | | | PERMITTED TO BE INSTALLED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | | | | 659-8096 EXT 8372 |
|