Plan Review Notes
Plan Review Notes For Permit 00080936
Permit Number 00080936
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************* REVISION REQUESTED *******
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 PANEL FOR GARAGE. MAIN BRKR? A MAIN
 MEANS OF DISCONNECT IS REQ`D.
  
 2)NOTE: PLEASE SHOW GROUNDING PER NEC
 FOR DETACHED GARAGE. COLD WATER,GRND ROD
  
 3)NOTE: PLEASE SEE REQ`MENTS FOR SD`S
 INSIDE SLEEPING ROOMS! NFPA-72 2-2.1.1.1
  
 4)NOTE: PLEASE PROVIDE A GFI REC OUTSIDE
 PER 210-52E
  
 THE FOLLOWING ARE NOTES TO QUESTION
 ANY OTHER ISSUES THAT MAY ARISE.
 IS THERE GOING TO BE CATV OR TELEPHONE
 OUTLETS INSTALLED??
 WHERE IS THE HOT WATER COMING FROM?
 PLEASE CLARIFY!
 IS THERE GOING TO BE CENTRAL A/C OR IS
 THERE GOING TO BE A WINDOW UNIT?
 PLEASE PROVIDE CLARIFICATION ON THE
 ABOVE INFORMATION.
  
 ALSO PLEASE NOTE THAT PROVISIONS FOR
 KITCHEN COOKING EQUIPMENT WILL NOT BE
 PERMITTED TO BE INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
  
 659-8096 EXT 8372