Plan Review Notes
Plan Review Notes For Permit 00080930
Permit Number 00080930
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD BASED ON SQ.FT.OF
 HABITABLE FLOOR SPACE PER SPC TABLE 407.
 SEE SPC.SEC.407.1.3 FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 2)DESIGN OF GREASE TRAP SHALL COMPLY W/
 CITY OF WPB BUILDING DEPT.REQS.(SEE
 ATTACHED).CONTACT ROD COMPO AT
 (561)835-7423 FOR APPROVAL OF SIZE.
 SUBMIT APPROVAL FORM FROM UTILITIES DEPT
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 3)SUBMIT A COMPLETE GAS RISER DIAGRAM
 FOR REVIEW.SHOW ALL EQUIPMENT ON THE GAS
 RISER DIAGRAM.COMPLY W/ATTACHED GAS REQS
  
 4)VACUUM RELIEF VALVE ON WATER HEATER
 IS NOT PROPERLY CONNECTED.INSTALLATION
 SUBJECT TO FIELD INSPECTOR'S APPROVAL.
 SPC SEC.507.1.2.
  
 5)PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL PRIOR TO APPROVAL BY THIS DEPT.
 CALL (954)958-5520.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.7.
  
 6)SHT.K-2 LISTS CONNECTION OF GAS EQUIP.
 W/GAS HOSE.GAS HOSE IS PROHIBITED PER
 SGC SEC.403.2.COMPLY W/SGC SEC.403.1.1.
  
 7)RELIEF DRAIN FOR EWH SHALL DISCHARGE
 INTO A FLOOR SINK,NOT A FLOOR DRAIN PER
 SPC SEC.804.1.,807.1.3.
  
 8)IF YOUR OCCUPANT LOAD REMAINS AT 120
 PERSONS ADDITIONAL PLUMBING FIXTURES
 WILL BE REQD.PER SPC TABLE 407.