| 2001-01-08 00:00:00 | 1)SUBMIT OCCUPANT LOAD BASED ON SQ.FT.OF |
| | HABITABLE FLOOR SPACE PER SPC TABLE 407. |
| | SEE SPC.SEC.407.1.3 FOR ALLOWED |
| | DEDUCTIBLE AREAS. |
| | |
| | 2)DESIGN OF GREASE TRAP SHALL COMPLY W/ |
| | CITY OF WPB BUILDING DEPT.REQS.(SEE |
| | ATTACHED).CONTACT ROD COMPO AT |
| | (561)835-7423 FOR APPROVAL OF SIZE. |
| | SUBMIT APPROVAL FORM FROM UTILITIES DEPT |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 |
| | |
| | 3)SUBMIT A COMPLETE GAS RISER DIAGRAM |
| | FOR REVIEW.SHOW ALL EQUIPMENT ON THE GAS |
| | RISER DIAGRAM.COMPLY W/ATTACHED GAS REQS |
| | |
| | 4)VACUUM RELIEF VALVE ON WATER HEATER |
| | IS NOT PROPERLY CONNECTED.INSTALLATION |
| | SUBJECT TO FIELD INSPECTOR'S APPROVAL. |
| | SPC SEC.507.1.2. |
| | |
| | 5)PLANS SHALL BE ROUTED TO DEPT.OF |
| | BUSINESS REGULATION FOR REVIEW AND |
| | APPROVAL PRIOR TO APPROVAL BY THIS DEPT. |
| | CALL (954)958-5520.COUNTYWIDE AMENDMENTS |
| | TO SPC SEC.101.4.7. |
| | |
| | 6)SHT.K-2 LISTS CONNECTION OF GAS EQUIP. |
| | W/GAS HOSE.GAS HOSE IS PROHIBITED PER |
| | SGC SEC.403.2.COMPLY W/SGC SEC.403.1.1. |
| | |
| | 7)RELIEF DRAIN FOR EWH SHALL DISCHARGE |
| | INTO A FLOOR SINK,NOT A FLOOR DRAIN PER |
| | SPC SEC.804.1.,807.1.3. |
| | |
| | 8)IF YOUR OCCUPANT LOAD REMAINS AT 120 |
| | PERSONS ADDITIONAL PLUMBING FIXTURES |
| | WILL BE REQD.PER SPC TABLE 407. |