Plan Review Notes
Plan Review Notes For Permit 00080930
Permit Number 00080930
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1. PROVIDE CFM VALUES AND ALL DUCT SIZES
 2. PROVIDE INFORMATION ON EQUIPMENT SCHE
 DULE INCLUDING SEER AND OUTSIDE AIR
 3. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED WITH NOTIFICATION BY BLDG ALARM
 OR HORN AND STROBE PER NFPA 90A 4.4-4.
  
 INFORMATION TO BE SUBMITTED PRIOR TO
 FINAL INSPECTION