| Date |
Text |
| 2001-01-08 00:00:00 | 1)HANDICAP STALLS SHALL COMPLY W/FACBC |
| | SEC.4.17.3.(MIN.WIDTH SHALL BE 83"IF |
| | LAV.IS ADJACENT TO W.C.)SEE 4.1.6.(B) |
| | |
| | 2)SUBMIT OCCUPANT LOAD BASED ON SQ.FT.OF |
| | HABITABLE FLOOR SPACE PER SPC TABLE 407. |
| | SEE SPC SEC.407.1.3.FOR ALLOWED |
| | DEDUCTIBLE AREAS. |
| | |
| | 3)DISHWASHER AND GARBAGE DISPOSAL SHALL |
| | BYPASS GREASY WASTE AND CONNECT TO |
| | SANITARY SYSTEM PERCITY ORDINANCE. |
| | |
| | 4)DESIGN OF GREASE TRAP SHALL COMPLY W/ |
| | BUILDING DEPT.REQS. (SEE ATTACHED) |
| | CONTACT ROD COMPO AT 561-835-7423 FOR |
| | APPROVAL OF SIZE.SUBMIT APPROVAL FORM |
| | FROM UTILITIES. |
| | |
| | 5)SHOW ALL EQUIPMENT ON GAS DRAWING.SEE |
| | ATTACHED FOR REQS. |
| | |
| | 6)SHUT-OFF VALVE,AUTOMATIC GAS VALVE( |
| | FIRE VALVE)AND UNION SHALL BE INSTALLED |
| | BELOW CEILING AND BE ACCESSIBLE.NFPA |
| | 5.5.4. |
| | |
| | 7)GREASY WASTE DESIGN SHALL COMPLY W/ |
| | SPC SEC.921. |
| | |
| | 8)SHT.P-1-BOTTOM FED WATER HEATER SHALL |
| | BE EQUIPPED W/VACUUM RELIEF VALVE PER |
| | SPC SEC.507.1.2. |
| | |
| | 9)SHT.P-4-WATER CLOSETS AND FIXTURE |
| | BRANCHES NOT PERMITED ON WET VENTS PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1 |
| | |
| | 10)HUB DRAINS NOT PERMITTED.REVISE TO |
| | FLOOR DRAIN. |
| | |
| | 11)SHT.P-4-FLAT DRY VENT NOT PERMITTED |
| | FOR CAN WASH. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |