Plan Review Notes
Plan Review Notes For Permit 00080930
Permit Number 00080930
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)HANDICAP STALLS SHALL COMPLY W/FACBC
 SEC.4.17.3.(MIN.WIDTH SHALL BE 83"IF
 LAV.IS ADJACENT TO W.C.)SEE 4.1.6.(B)
  
 2)SUBMIT OCCUPANT LOAD BASED ON SQ.FT.OF
 HABITABLE FLOOR SPACE PER SPC TABLE 407.
 SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 3)DISHWASHER AND GARBAGE DISPOSAL SHALL
 BYPASS GREASY WASTE AND CONNECT TO
 SANITARY SYSTEM PERCITY ORDINANCE.
  
 4)DESIGN OF GREASE TRAP SHALL COMPLY W/
 BUILDING DEPT.REQS. (SEE ATTACHED)
 CONTACT ROD COMPO AT 561-835-7423 FOR
 APPROVAL OF SIZE.SUBMIT APPROVAL FORM
 FROM UTILITIES.
  
 5)SHOW ALL EQUIPMENT ON GAS DRAWING.SEE
 ATTACHED FOR REQS.
  
 6)SHUT-OFF VALVE,AUTOMATIC GAS VALVE(
 FIRE VALVE)AND UNION SHALL BE INSTALLED
 BELOW CEILING AND BE ACCESSIBLE.NFPA
 5.5.4.
  
 7)GREASY WASTE DESIGN SHALL COMPLY W/
 SPC SEC.921.
  
 8)SHT.P-1-BOTTOM FED WATER HEATER SHALL
 BE EQUIPPED W/VACUUM RELIEF VALVE PER
 SPC SEC.507.1.2.
  
 9)SHT.P-4-WATER CLOSETS AND FIXTURE
 BRANCHES NOT PERMITED ON WET VENTS PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 10)HUB DRAINS NOT PERMITTED.REVISE TO
 FLOOR DRAIN.
  
 11)SHT.P-4-FLAT DRY VENT NOT PERMITTED
 FOR CAN WASH.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.