| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO BUILDING ADDRESS SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | | COMPLY WITH CITY CODE REQUIREMENTS. | | | 2) ENTRY DOORS MUST SWING IN THE | | | DIRECTION OF EXIT TRAVEL. | | | 3) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 4) ALL EXIT DOORS SUBJECT TO AN | | | OCCUPANCY OF 100 OR MORE PERSONS ARE | | | TO BE EQUIPPED WITH APPROVED PANIC | | | HARDWARE. NO OTHER LOCKS WILL BE | | | PERMITTED. | | | 5) INTERIOR FINISHES SHALL BE CLASS | | | A OR B IN EXITS. INTERIOR FINISHES IN | | | OTHER AREAS SHALL BE CLASS A,B,OR C. | | | 6) PROVIDE COMPLETE PLANS FOR THE | | | INSTALLATION OF THE HOOD, DUCT, AND | | | EXTINGUISHING SYSTEM. A SEPARATE PERMIT | | | IS REQUIRED. | | | 7) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 8) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 9) NO FIRE SPRINKLER DRAWINGS SUBMITTED | | | WITH PLANS. ACCORDING TO FIRE RESCUE | | | RECORDS, THIS BUILDING HAS AN EXISTING | | | FIRE SPRINKLER SYSTEM. |
|