Plan Review Notes
Plan Review Notes For Permit 00080930
Permit Number 00080930
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO BUILDING ADDRESS SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) ENTRY DOORS MUST SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 3) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 4) ALL EXIT DOORS SUBJECT TO AN
 OCCUPANCY OF 100 OR MORE PERSONS ARE
 TO BE EQUIPPED WITH APPROVED PANIC
 HARDWARE. NO OTHER LOCKS WILL BE
 PERMITTED.
 5) INTERIOR FINISHES SHALL BE CLASS
 A OR B IN EXITS. INTERIOR FINISHES IN
 OTHER AREAS SHALL BE CLASS A,B,OR C.
 6) PROVIDE COMPLETE PLANS FOR THE
 INSTALLATION OF THE HOOD, DUCT, AND
 EXTINGUISHING SYSTEM. A SEPARATE PERMIT
 IS REQUIRED.
 7) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 8) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 9) NO FIRE SPRINKLER DRAWINGS SUBMITTED
 WITH PLANS. ACCORDING TO FIRE RESCUE
 RECORDS, THIS BUILDING HAS AN EXISTING
 FIRE SPRINKLER SYSTEM.