| Plan Review Notes For Permit 00080930 |
| Permit Number |
00080930 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | A. SHEET CS1 | | | 1. CODE REFERENCES, CORRECT THE | | | FOLLOWINF, | | | MECHANICIAL CODE IS 1997 NOT 1994 | | | BUILDING CODE IS 1997 NOT 1999 | | | ELECTRICAL CODE IS 1999 NOT 1996 | | | | | | B. SHEET CS2 | | | 1. NOTE #7 REFERS TO WRONG ACCESSABILITY | | | CODE PROPER REFERENCE IS TO FLORIDA | | | ACCESSABILITY CODE 1997 EDITION | | | | | | C. SHEET A1 | | | 1. SIGNS ARE NOT COVERED BY PRIME PERMIT | | | SUBMIT SEPERATE APPLICATION FOR PERMIT. | | | | | | D. SHEET A3 NOTES INDICATE EXTERIOR STUD | | | 1. NOTES INDICATE EXTERIOR STUD WALLS | | | THIS BUILDING IS IN THE FIRE DISTRICT | | | USE OF WOOD IS A VIOLATION OF 1997 SBC | | | SECTION F102.1, REVISE. | | | 2. NOTE ON STRUCTURAL, ALL STRUCTURAL | | | VERIFICATION IS TO BE PERFORMED BY A | | | FLORIDA LICENSED ENGINEER OR ARCHITECT. | | | | | | E. SHEET A5 | | | 1. DETAIL C, HAVE STRUCTURAL ENGINEER | | | CERTIFY LOADING OF BOTTOM CORD OF ROOF | | | TRUSSES WITH WOOD BEAM AND CELING. |
|