Plan Review Notes
Plan Review Notes For Permit 00080910
Permit Number 00080910
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE F.A.C ONLY THE ARCH/
 ENGINEER OF RECORD CAN MAKE CHANGES TO
 SIGNED AND SEALED PLANS. THIS IS STATE
 LAW AND VIOLATES 61G16 AND 481 OF
 F.A.C
  
 ALSO PLEASE NOTE THAT THE COPIES OF THE
 NATIONAL ELECTRIC CODE THAT WERE SUB-
 -MITTED FOR MY REVIEW WERE OUT OF THE
 "96" NEC. WE ARE IN THE "99" NEC AND
 HAVE BEEN SINCE MARCH 1ST OF 2000.
 PLEASE SEE ALL THE CODE ARTS IN THE"99"
 FOR MY REFERENCES.
  
 PLEASE SUBMIT PLANS WITH ALL THE ABOVE
 INFORMATION CORRECTED AND DONE BY THE
 ARCH. OF RECORD. SIGNED, SEALED AND
 DATED PER F.A.C. 481.221.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372
  
  
 ALSO PLEASE NOTE THAT PLANS ARE STAMPED
 BY ARCH. THIS IS UNACCEPTABLE PER FS.
 WET SIGNATURE,RAISED SEALED AND DATED!!
 481.221