| 2001-01-08 00:00:00 | ****************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE 210-8-A-6 FOR OUTLETS |
| | SERVING KITCHEN COUNTERSPACE. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1. |
| | FOR SMOKE DETECTORS INSIDE AND OUTSIDE |
| | BEDROOMS AND IN BEDROOM #3 NOW THAT |
| | WORK IS BEING DONE IN THERE. |
| | |
| | 3)NOTE: PLEASE SEE 215-5 FOR ALL THE |
| | INFORMATION REQ`D ON LOAD CALCULATIONS/ |
| | RISER DIAGRAM ETC. |
| | |
| | 4)NOTE: PLEASE SEE 230-72 FOR GROUPING |
| | OF MAINS. MAINS TO BE GROUPED. |
| | |
| | 5)NOTE: PLEASE SEE THAT YOU SHOW ON |
| | RISER DIAGRAM PANEL BEING EXISTING AND |
| | NEW.???? PLEASE CLARIFY. |
| | |
| | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. PER |
| | 110-9 AND 215-5. |
| | |
| | 7)NOTE:PLEASE SEE 210-11-C-3 FOR THE |
| | REQ`D BATH(S) CIRCUIT(S) TO BE LISTED ON |
| | PANEL SCHEULE. |
| | |
| | 8)NOTE: PLEASE SEE PIPE FILL FOR 1 1/4 |
| | SCHED 80 PVC. SEE ALL THE WIRE BEING |
| | SHOWN. |
| | |
| | 9)NOTE: PLEASE SEE 250-50 FOR GROUNDING |
| | ELECTRODE SYSTEM. PLEASE SHOW AND INCL- |
| | -UDE BLDG.STEEL AND COLD WATER PIPE. |
| | |
| | 10)NOTE: PLEASE SHOW LOCATION OF NEW |
| | PANEL BEING INSTALLED FOR THE ADDITION. |
| | |
| | 11)NOTE: PLEASE SEE 110-26 FOR CLEARENCE |
| | REQ`MENTS IN CLOSET IN MASTER/ALCOVE |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. PLEASE NOTE THAT IF THERE |
| | ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW. |
| | 659-8096 EXT 8372 |