2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SECS.4.1.3.(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 2)ACCESSIBLE TOILET STALLS WITHIN THE
 RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3
 FOR SIZE.
  
 3)SINK IN LOUNGE SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 4)SUBMIT A SANITARY RISER DIAGRAM THAT
 COMPLIES W/SPC IN ALL RESPECTS.SEE
 BELOW:
 A)WATER CLOSETS NOT PERMITTED ON WET
 VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 B)FLAT,DRY VENTS ARE NOT PERMITTED PER
 SPC SEC.906.2.1.
  
 C)MOP SINK NOT PROPERLY VENTED.SPC SEC.
 906.2.1.
  
 D)FLOOR DRAINS SHALL BE EQUIPPED W/TRAPS
 PER SPC 901.2.
  
 E)WATER CLOSETS ARE NOT PROPERLY VENTED.
 SPC 901.2,COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.3.
  
 5)MIN.SIZE OF DRAINAGE SYSTEM UNDER-
 GROUND SHALL BE 2"PER SPC SEC.714.4.
  
 6)OVER 2 FIXTURES ARE SUPPLIED BY 1/2"
 C.W.(SEE MOP SINK AREA.)PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.607.7.
  
 7)COMPILE SHEETS INTO 2 COMPLETE SETS OF
 PLANS AND VOID OLD SHEETS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.