Plan Review Notes
Plan Review Notes For Permit 00080866
Permit Number 00080866
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)ALL PUBLIC AND COMMON AREA TOILET
 ROOMS SHALL BE FULLY ACCESSIBLE PER
 FACBC SEC.4.1.3.(11).(SEE TOILET ROOM AT
 RECEPTION AREA.)
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SECS.4.1.3(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 3)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.1.1.
  
 4)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.SUPPLY PERMANENT
 LADDER OR RELOCATE HEATER TO FLOOR.
  
 5)ACCESSIBLE TOILET STALLS WITHIN THE
 RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3
 (MIN.SIZE TO BE 83" IF LAV.IS ADJACENT
 TO WATER CLOSET.FACBC SEC.4.22.4.
  
 6)SINK IN LOUNGE SHALL COMPLY W/FACBC
 SECS.4.24.1-4.24.7.
  
 7)REMOVE TRAP FROM PAN DRAIN AND PIPE
 DRAIN TO APPROVED LOCATION PER SPC SEC.
 507.8.2.
  
 8)RELIEF VALVE SHALL NOT DRAIN INTO PAN
 PER COUNTYWIDE AMENDMENTS SEC.507.8.4.
  
 9)SUBMIT A REVISED SANITARY RISER
 DIAGRAM THAT COMPLIES W/SPC IN ALL
 RESPECTS.THERE ARE TOO MANY CODE VIOLAT-
 IONS ON THE DRAWING TO LIST.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.