| 2001-01-08 00:00:00 | 1)ALL PUBLIC AND COMMON AREA TOILET |
| | ROOMS SHALL BE FULLY ACCESSIBLE PER |
| | FACBC SEC.4.1.3.(11).(SEE TOILET ROOM AT |
| | RECEPTION AREA.) |
| | |
| | 2)A DRINKING FOUNTAIN IS REQD.PER SPC |
| | TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC |
| | SECS.4.1.3(10)(A),4.15.PROVISIONS SHALL |
| | BE MADE FOR PEOPLE WHO HAVE TROUBLE |
| | BENDING OR STOOPING. |
| | |
| | 3)FLOOR DRAINS ARE REQD.IN THE TOILET |
| | ROOMS PER SPC SEC.409.1.1. |
| | |
| | 4)WATER HEATER SHALL BE READILY ACCESS- |
| | IBLE PER SPC SEC.501.7.SUPPLY PERMANENT |
| | LADDER OR RELOCATE HEATER TO FLOOR. |
| | |
| | 5)ACCESSIBLE TOILET STALLS WITHIN THE |
| | RESTROOM SHALL COMPLY W/FACBC SEC.4.17.3 |
| | (MIN.SIZE TO BE 83" IF LAV.IS ADJACENT |
| | TO WATER CLOSET.FACBC SEC.4.22.4. |
| | |
| | 6)SINK IN LOUNGE SHALL COMPLY W/FACBC |
| | SECS.4.24.1-4.24.7. |
| | |
| | 7)REMOVE TRAP FROM PAN DRAIN AND PIPE |
| | DRAIN TO APPROVED LOCATION PER SPC SEC. |
| | 507.8.2. |
| | |
| | 8)RELIEF VALVE SHALL NOT DRAIN INTO PAN |
| | PER COUNTYWIDE AMENDMENTS SEC.507.8.4. |
| | |
| | 9)SUBMIT A REVISED SANITARY RISER |
| | DIAGRAM THAT COMPLIES W/SPC IN ALL |
| | RESPECTS.THERE ARE TOO MANY CODE VIOLAT- |
| | IONS ON THE DRAWING TO LIST.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |