Plan Review Notes
Plan Review Notes For Permit 00080866
Permit Number 00080866
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH ALL
 BRANCH CIRCUIT #`S SHOWN ON LAYOUT.
 PLEASE SUBMIT A PANEL SCHEDULE TO
 CORRELATE WITH LAYOUT AND BRANCH CIRCUIT
 #`S.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTION
 SHOWING ALL CONTINUOUS LOADS AT 125%
 (LIGHTING)/(SIGNAGE) ECT.
 THE LOAD IS SHOWN AT 200 AMPS? PLEASE
 SHOW LOAD CALCS PER 220. MAIN DISC IS
 RATED FOR 200A.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372