| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ALL | | | BRANCH CIRCUIT #`S SHOWN ON LAYOUT. | | | PLEASE SUBMIT A PANEL SCHEDULE TO | | | CORRELATE WITH LAYOUT AND BRANCH CIRCUIT | | | #`S. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCUALTION | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING)/(SIGNAGE) ECT. | | | THE LOAD IS SHOWN AT 200 AMPS? PLEASE | | | SHOW LOAD CALCS PER 220. MAIN DISC IS | | | RATED FOR 200A. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|