Plan Review Notes
Plan Review Notes For Permit 00080861
Permit Number 00080861
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST RE-
 VIEW. PANEL SCHEDULE SHOWED ONE SIZE FOR
 PANEL"F" MCB AND RISER SHOWED ANOTHER.
 IN YOUR RESPONSE LETTER DATED 9/21/00
 YOU RESOND SAYING PANEL"F" IS SHOWN AT
 300 A. PLEASE SEE E3-3 PANEL AND RISER
 DIAGRAM IS SHOWN DIFFERENT FROM YOUR
 RESPONSE. IT IS OK TO INSTALL A 400A
 MCB PANEL BUT THE FEEDERS ARE ONLY RATED
 FOR 310 AMPS UNDER 310-16 75: COLUMN.
 PLEASE SEE MAX OCP FOR 310A WIRE. ALSO
 SEE 240-6 FOR STANDARD BRKR SIZES.
 PLEASE DECREASE MCB SIZE FOR PANEL"F"
 OR INCREASE WIRE SIZE.
  
 ALL OTHER NOTES FROM FIRST REVIEW WERE
 ADDRESSED. PLEASE SUBMIT THE ABOVE INFOR
 -MATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS ON REVIEW COMMENTS PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372