2001-01-08 00:00:00**************DENIED********************
 1. OUTSIDE AIR REQUIREMENTS FROM ASHRAE
 62-89 SHALL NOT BE REDUCED BELOW MINIMUM
 REQUIRED WITH C02 SENSOR. SHOW SPECIFIC
 CALCULATIONS SHOWING MAXIMUM AND MINIMUM
 AMOUNTS PROVIDED AT FULL RANGE OF DAMPER
 ACTIVITY PROVIDING MINIMUM AMOUNT OF
 OUTSIDE AIR TO EQUAL ASHRAE 62-89 TABLE
 2 QUANTITY.
 2.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3.PROVIDE INFORMATION ON EXHAUST AIR FAN
 MODEL, CFM, HANGING DETAIL ETC.