| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE E3-4 AND E3-3. PLEASE | | | GIVE CLARIFICATION ON MCB FOR PANEL "F". | | | ONE SHOWS 300A AND THE OTHER 400A. | | | | | | 2)NOTE: PLEASE SEE ARTS:220-3-B-7/220-12 | | | -A,/ 210-62 FOR THE REQ`MENTS FOR SHOW | | | WINDOWS. | | | | | | 3)NOTE:PLEASE PROVIDE INFORMATION ON | | | ENGINEER OF RECORD.TITLE BLOCK | | | | | | 4)NOTE; PLEASE 3-3 AND 3-4, YOU SHOW TWO | | | DIFFERENT SIZE TRANSFORMERS? PLEASE | | | SHOW THE CORRECT SIZE. | | | ALSO PLEASE SHOW OCP OF TRANSFORMER. NO | | | SIZE SHOWN ON PLANS FOR BREAKER. | | | | | | 5)NOTE: PLEASE SEE E4-0 FOR COLOR CODING | | | OF FEEDERS PER LOCAL CODE 215. | | | 277/480 BROWN, PURPLE, YELLOW,GRAY. | | | | | | 6)NOTE: PLEASE SEE LOCAL AMENDMENTS FOR | | | OUTLET SPACING OF EVERY 20` OF WALL. | | | THIS IS FOR SALES AREA. ART 210-50 | | | | | | 7)NOTE: PLEASE NOTE THAT ON 3-3 ON | | | PANELS "C","D" THE REFERENCED CODE ART | | | DOES NOT EXIST UNDER THE "99" NEC. | | | PLEASE CHECK AND VERIFY. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMAITON | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|