2001-01-08 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE E3-4 AND E3-3. PLEASE
 GIVE CLARIFICATION ON MCB FOR PANEL "F".
 ONE SHOWS 300A AND THE OTHER 400A.
  
 2)NOTE: PLEASE SEE ARTS:220-3-B-7/220-12
 -A,/ 210-62 FOR THE REQ`MENTS FOR SHOW
 WINDOWS.
  
 3)NOTE:PLEASE PROVIDE INFORMATION ON
 ENGINEER OF RECORD.TITLE BLOCK
  
 4)NOTE; PLEASE 3-3 AND 3-4, YOU SHOW TWO
 DIFFERENT SIZE TRANSFORMERS? PLEASE
 SHOW THE CORRECT SIZE.
 ALSO PLEASE SHOW OCP OF TRANSFORMER. NO
 SIZE SHOWN ON PLANS FOR BREAKER.
  
 5)NOTE: PLEASE SEE E4-0 FOR COLOR CODING
 OF FEEDERS PER LOCAL CODE 215.
 277/480 BROWN, PURPLE, YELLOW,GRAY.
  
 6)NOTE: PLEASE SEE LOCAL AMENDMENTS FOR
 OUTLET SPACING OF EVERY 20` OF WALL.
 THIS IS FOR SALES AREA. ART 210-50
  
 7)NOTE: PLEASE NOTE THAT ON 3-3 ON
 PANELS "C","D" THE REFERENCED CODE ART
 DOES NOT EXIST UNDER THE "99" NEC.
 PLEASE CHECK AND VERIFY.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372