| Plan Review Notes For Permit 00080850 |
| Permit Number |
00080850 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) ON AUGUST 16, 2000, WRITER SPOKE | | | TO JOE CIPOLETTO OF ALARM GUARD BY | | | TELEPHONE. WRITER ASKED WHAT TYPE OF | | | WIRE IS TO BE USED HE RESPONDED 18 | | | GAUGE, 4 CONDUCTOR, FPL 2204PP-2, RED | | | FIRE WIRE. | | | 2) SMOKE DETECTORS ARE TO BE INSTALLED | | | A MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 3) MANUAL PULL STATIONS SHALL BE | | | MOUNTED NO LOWER THAN 3 1/2 FEET AND NO | | | MORE THAN 4 1/2 FEET FROM THE FLOOR. | | | 4) HORN STROBE DEVICES TO BE MOUNTED | | | BETWEEN 80-96 INCHES ABOVE THE FLOOR ON | | | WALLS. | | | 5) SYSTEM SUBJECT TO COMPLETE | | | INSPECTION AFTER INSTALLATION BY FIRE | | | RESCUE. |
|