Plan Review Notes
Plan Review Notes For Permit 00080832
Permit Number 00080832
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT 2 COMPLETE SETS OF PLUMBING
 DRAWINGS FOR REVIEW.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 2)SIZE ALL THE VENTS ON THE ISOMETRIC.
 COMPLY W/SPC TABLE 920.2.
  
 3)SUBMIT SQUARE FEET OF HABITABLE FLOOR
 SPACE.SEE SPC 407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 4)NOTE TOTAL NUMBER OF SEATS PROVIDED TO
 ENSURE COMPLIANCE W/SPC TABLE 407 FOR
 MINIMUM PLUMBING FIXTURES.
  
 5)WAINSCOTING TO 4' REQD.IN TOILET ROOMS
 PER SBC SEC.1204.2.
  
 6)SHT.A6.3-T.P.DISPENSER SHALL BE
 MOUNTED 19"TO CENTER,NOT BOTTOM PER
 FACBC FIG.29.
  
 7)ONLY 2 FIXTURES PERMITTED TO BE
 SUPPLIED BY 1/2"CW LINE.COUNTYWIDE AMEND
 MENTS TO SPC SEC.607.7
  
 8)RELIEF LINE CANNOT DRAIN INTO PAN PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.4
  
 9)SUBMIT WAIVER FROM CITY OF WPB
 UTILITIES FOR DELETION OF CONNECTION TO
 GREASE INTERCEPTOR.CONTACT R.COMPO AT
 561-835-7423.
  
 10)SIZE ALL PLBG.VENTS ON THE DRAWING.
  
 11)BACK TO BACK WATER COSETS SHALL BE
 VENTED PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.