Plan Review Notes For Permit 00080832
Permit Number 00080832
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********DENIED**********************
  
 1.OUTSIDE AIR SUPPLIED DOES NOT MEET
 ASHRAE 62-89 (34PERSON X 20CFM EA =680CF
 M)PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE EXHAUST FAN CAPACITY IN CFM
 NOTE:
 NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM AREA
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO HORN AND STROBE FOR NOTI-
 FICATION PER NFPA 90A 4-4.4