| Plan Review Notes For Permit 00080832 |
| Permit Number |
00080832 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED********************** | | | | | | 1.OUTSIDE AIR SUPPLIED DOES NOT MEET | | | ASHRAE 62-89 (34PERSON X 20CFM EA =680CF | | | M)PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2. PROVIDE EXHAUST FAN CAPACITY IN CFM | | | NOTE: | | | NO COMBUSTIBLES ALLOWED IN RETURN AIR | | | PLENUM AREA | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | TO BE TIED TO HORN AND STROBE FOR NOTI- | | | FICATION PER NFPA 90A 4-4.4 |
|