Plan Review Notes For Permit 00080832
Permit Number 00080832
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING
 DETAIL FOR TRANSFORMER BEING INSTALLED.
 PLEASE SEE 450-21-B FOR INSTALLATION
 DETAILS AND REQ`MENTS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER ART;220 OF NEC. CLARIFY LOAD CALCS
 FOR TRACK LIGHTING PER 220-12-B. PLEASE
 SHOW SQ FT ON LOAD CALCS AND ALL CONTIN-
 -UOUS LOADS AT 125%.
 PLEASE SHOW LOAD ON LINE SIDE OF MAIN
 TRANSFORMER FEEDING STARBUCKS.
 PROVIDE CONDUCTOR SIZES. 215-5
  
 3)NOTE:PANEL "A" IS REQ`D TO BE MCB ON
 LOAD SIZE OF TRANSFORMER AS IT IS A
 SEPARATELY DERIVED SYSTEM.
  
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.