 1. SHEET A4.0-TOTAL SQUARE FOOTAGE IS
 2065, AREA CALCULATIONS INDICATE 1426 ?
 2. OCCUPANCY COUNT ON SHEET A1.0 MUST BE
 CORECTED TO REFLECT CORECT OCCUPANCY
 LOAD.
 EXAMPLE: SEATING IS SHOWN ON A1.0 FOR
 11 PEOPLE, ACTUAL SEATING COUNT IS 32
 PEOPLE.
 3.SHEET A1.0- 1997 SBC SECTION 1004.1.2
 TWO MEANS OF EGRESS REQUIRED, CORRECTED
 OCCUPANCY COUNT-SEATING 32+21+2=55 TOTAL
 4.EXIT COURIDOR TO BE A MIMIMIN 44"
 1997 SBC TABLE 1004
 5.REAR EXIT DOOR TO COMPLY WITH 1997 SBC
 SECTION 1003.2 AND ASSOCIATED SUBSECTION
 6.PLANS INDICATE LOCATION IN BROWERD CO
 CORRECT PLANS TI REFLECT PALM BEACH CO.
 7.PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOWS AND DOORS FOR STORE-
 FRONT/METRO DADE COUNTY OR SBCCI
 8.FLORIDA ENERGY SHEETS MUST BE COMPLETE
 AND BE SIGNED BY OWNER/AGENT.
 9.SUBMIT FIRE SPRINKLER PLANS AND PERMIT
 APPLICATION.
 10.DEMIZING WALL MUST BE COMPLETED ON
 BOTH SIDES PRIOR TO C.O. BEING ISSUED.