| Plan Review Notes For Permit 00080832 |
| Permit Number |
00080832 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | 1. SHEET A4.0-TOTAL SQUARE FOOTAGE IS | | | 2065, AREA CALCULATIONS INDICATE 1426 ? | | | 2. OCCUPANCY COUNT ON SHEET A1.0 MUST BE | | | CORECTED TO REFLECT CORECT OCCUPANCY | | | LOAD. | | | EXAMPLE: SEATING IS SHOWN ON A1.0 FOR | | | 11 PEOPLE, ACTUAL SEATING COUNT IS 32 | | | PEOPLE. | | | 3.SHEET A1.0- 1997 SBC SECTION 1004.1.2 | | | TWO MEANS OF EGRESS REQUIRED, CORRECTED | | | OCCUPANCY COUNT-SEATING 32+21+2=55 TOTAL | | | 4.EXIT COURIDOR TO BE A MIMIMIN 44" | | | 1997 SBC TABLE 1004 | | | 5.REAR EXIT DOOR TO COMPLY WITH 1997 SBC | | | SECTION 1003.2 AND ASSOCIATED SUBSECTION | | | 6.PLANS INDICATE LOCATION IN BROWERD CO | | | CORRECT PLANS TI REFLECT PALM BEACH CO. | | | 7.PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT WINDOWS AND DOORS FOR STORE- | | | FRONT/METRO DADE COUNTY OR SBCCI | | | 8.FLORIDA ENERGY SHEETS MUST BE COMPLETE | | | AND BE SIGNED BY OWNER/AGENT. | | | 9.SUBMIT FIRE SPRINKLER PLANS AND PERMIT | | | APPLICATION. | | | 10.DEMIZING WALL MUST BE COMPLETED ON | | | BOTH SIDES PRIOR TO C.O. BEING ISSUED. |
|