Plan Review Notes
Plan Review Notes For Permit 00080776
Permit Number 00080776
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED PER TONY MARCELLO 9-13-00
  
 1)ON THE FOOTING SCHEDULE IS THE TE2
 CHANGED OR CROSSED OUT? PLEASE CLARIFY
 FOR THE OPTIONAL CART GARAGE SHOWS A TE2
 THICKEN EDGE.IS THE TE1 AND THE TE2 THE
 SAME?
  
 2)PLEASE DESIGNATE THE EGRESS WINDOWS
 FOR THE SLEEPING ROOMS.
  
 3)TRUSSES #2128,1928 ETC. ON THE BEARING
 WALL SHOW AN UPLIFT OF 1147#.PLEASE
 RECHECK THE UPLIFT FOR THE SP6 AS CALLED
 FOR ON A7 DETAIL 9.
  
 4)PLEASE SHOW A CONNECTOR SCHEDULE FOR
 THE CONNECTORS THAT ARE CALLED FOR.
  
 5)DETAIL 2 ON SHEET A6 SIMCO RTPGA824
 WHAT IS THE UPLIFT VALUE AND THE NUMBER
 AND THE SIZE OF THE ANCHORS REQUIRED FOR
 THIS UPLIFT.