2001-01-08 00:00:001) ALL DEEP FAT FRYERS ARE TO HAVE
 HIGH-LIMIT CONTROLS AS PER NFPA 96,
 SECTION 9-2.
 2) PROVIDE SEPARATE PLANS AND PERMIT
 FOR WET CHEMICAL EXTINGUISHING SYSTEM.
 NO DRY-CHEMICAL EXTINGUISHING SYSTEMS
 WILL BE ALLOWED.
 3) PLEASE DEFINE TYPE OF COMBUSTIBLE
 MATERIAL DESCRIBED ON PLAN.
 4) TEST AND BALANCE REPORT REQUIRED AT
 TIME OF FINAL.
 5) HOOD, DUCT AND EXTINGUISHING SYSTEM
 SUBJECT TO FINAL INSPECTION BY
 MECHANICAL AND FIRE RESCUE DIVISIONS.