| Plan Review Notes For Permit 00080656 |
| Permit Number |
00080656 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) ALL DEEP FAT FRYERS ARE TO HAVE | | | HIGH-LIMIT CONTROLS AS PER NFPA 96, | | | SECTION 9-2. | | | 2) PROVIDE SEPARATE PLANS AND PERMIT | | | FOR WET CHEMICAL EXTINGUISHING SYSTEM. | | | NO DRY-CHEMICAL EXTINGUISHING SYSTEMS | | | WILL BE ALLOWED. | | | 3) PLEASE DEFINE TYPE OF COMBUSTIBLE | | | MATERIAL DESCRIBED ON PLAN. | | | 4) TEST AND BALANCE REPORT REQUIRED AT | | | TIME OF FINAL. | | | 5) HOOD, DUCT AND EXTINGUISHING SYSTEM | | | SUBJECT TO FINAL INSPECTION BY | | | MECHANICAL AND FIRE RESCUE DIVISIONS. |
|