Plan Review Notes
Plan Review Notes For Permit 00080584
Permit Number 00080584
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-29 00:00:00*************DENIED*********************
 1. SUBMIT DRAWINGS WHERE THE MECHANICAL
 ELECTRICAL AND ARCHITECTURAL MATCH IN
 USE AND LAYOUT. UNABLE TO REVIEW UNTIL
 DRAWINGS MATCH.
 2. PROVIDE INFORMATION ON EQUIPMENT
 INDICATING LOCATION AND TYPE. PROVIDE
 CURB INFO IF RTU OR PROVIDE PENETRATION
 INFO IF PACKAGE EQUIPMENT.
 PROVIDE INFO ON LOCATION OF
 CONDENSING UNITS FOR SPLIT SYSTEMS.
 MECHANICAL EQUIPMENT ON ROOF REQUIRES
 MINIMUM 18" OF CLEARANCE BETWEEN ROOF
 SURFACE AND BOTTOM OF EQUIPMENT STAND
 SUPPORT.
 3. PROVIDE INFO ON INSTALLATION OF AHU
 EQUIPMENT, CONDENSATE DRAIN, OVERFLOW
 PROTECTION, RETURN DUCT OR PLENUM, ETC.
 4. DOES DUCT RUN BETWEEN OLD TRUSSES OR
 NEW FLOOR ASSEMBLY.
 5. NEED INFORMATION ON FIRE PROTECTION
 OF ALL DUCTS PENETRATING RATED FLOORS,
 CEILING , OR WALLS.
 6. PROVIDE INFORMATION ON EXHAUST FANS
 REQUIRED FOR ALL BATHROOMS TO BE
 INSTALLED.
 7. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 8. PROVIDE AIR BALANCE SCHEDULE PER
 1997SMC 501.2