| 2001-01-22 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | THIS INFORMATION WAS GIVEN ON SHEET E-4 |
| | ON LAST SUBMITTAL BUT IS NOT SHOWN ON |
| | SHEET RE-4A ON THIS SUBMITTAL. PLEASE DO |
| | SO. |
| | |
| | 2)NOTE: PLEASE NOTE THAT UNDER F.A.C, |
| | SEC 481-.221 ALL HAND WRITTEN CHANGES ON |
| | PLANS ARE TO BE SIGNED AND DATED BY |
| | THEARCH/OF RECORD. PLEASE SEE E- SHEETS |
| | WITH BRANCH CIRCUIT #`S HAND WRITTEN |
| | IN. PLEASE REDRAW PLANS BEFORE |
| | RE-SUBMITTAL |
| | PER COUNTY-WIDE ADMINISTRATIVE CODE SEC |
| | 104.2.1 AND 104.2.7 |
| | |
| | 3)NOTE: PLEASE TRANSFER ATTACHED SHEETS |
| | CONTAINING LOAD CALCULATIONS AND PANEL |
| | SCHEDULES OF PANELS "A" AND "B". PLEASE |
| | HAVE THESE DRAWN ON PLANS AS ATTACHED |
| | SHEETS SEEM TO GET TORN OFF DURING |
| | CONSTRUCTION. IF THOSE ATTACHED SHEETS |
| | ARE PREPARED BY SOMEONE ELSE THEN UNDER |
| | C.A.C THEY ARE TO BE SIGNED ALSO. SEC |
| | 104.2.1. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-80096 EXT 8372 |