| 2001-01-19 00:00:00 | BUILDING PLAN REVIEW: |
| | 1)- SBC 104.2.2- ADDITIONAL INFO |
| | SHEET A-1 SHOWS A STAIRWAY AT THE BACK |
| | OF THE EXISTING BUILDING ON THE SECOND |
| | FLOOR PLAN, IS THIS STAIR BEING DELETED? |
| | IF NOT IT BLOCKS THE EGRESS ON THE |
| | EGRESS ON THE FIRST FLOOR CORRIDOR. THE |
| | SAME STAIRWAY SHOWS UP ON VARIOUS PLANS. |
| | 2)- SHEET A-3 SECTION "CC" SHOWS AN |
| | ADJACACEENT 2 STORY EXISTING WALL. THE |
| | DETAIL CALLS OUT FOR FOR UL DES U473 TO |
| | BE INSTALLED ATOP OF A STEEL BEAM. HOW |
| | WILL THE CEMENTITIOUS BACKER BOARD BE AT |
| | TACHED? THE SECOND QUESTION IS HOW WILL |
| | THE BOTTOM OF THE CEMENTITIOUS BOARD BE |
| | SEALED FOR FIRE PROOFING? THE THIRD ITEM |
| | IN THIS DETAIL IS A NOTE ON INSTALLING |
| | FIRE MASTER BOARD UL 723 IN THE UL LIST- |
| | ING BOOK X723 LIST A SPRAY TYPE OF INSUL |
| | ATION, WE NEED MORE INFORMATION FOR THIS |
| | 2 HR RATING? |
| | 3)- SHEET RA-6 SHOWS A DETAIL ON THE |
| | 1-HR RATED ACOUSTIC TILE CEILING, PLEASE |
| | PROVIDE INFORMATION ON THE TILE, FRAME |
| | AND TILE LOCKING OR HOLD DOWN. |
| | 4)- NOTE: THE PLANS INDICATE THAT THE |
| | SECOND FLOOR WILL BE USED FOR STORAGE |
| | PURPOSES ONLY, TAKING THE EXCEPTION OF |
| | NO ELEVATOR REQUIRED BY THE FL. ACCESS- |
| | IBILITY CODE. IF THE TENANT OCCUPANCY |
| | USAGE CHANGES TO A HABITABLE SPACE A |
| | ELEVATOR WOULD BE REQUIRED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |