Plan Review Notes
Plan Review Notes For Permit 00080584
Permit Number 00080584
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SHT.SP-1-WATER CLOSETS AND FIXTURE
 BRANCHES ARE NNOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 2)RELIEF LINE AND PAN DRAIN FOR WATER
 HEATER SHALL DISCHARGE TO EXTERIOR PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.6.1
 507.8.3.
  
 3)PAN DRAIN AND PAN SHALL COMPLY W/SPC
 SEC.507.8.2.
  
 4)SHT.SP-1- SANITARY RISER SHOWS 2 LAVS
 ON 2ND FLOOR AND SHT.A-2 SHOWS FULL BATH
 SHOW ALL NEW PLUMBING ON THE SANITARY
 RISER.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 5)SHT.A-5-PLANS SHOW 8"STORM DRAIN
 DISCHARGING INTO 6"LINE.SPC SEC.307.5.
  
 6)INDICATE SLOPE OF STORM DRAIN PIPING
 ON PLANS.COMPLY W/SPC TABLE 1108.1,
 1108.2.
  
 7)SHOW SQ.FT.AREA OF ROOF DRAINED BY EA.
 ROOF DRAIN.COMPLY W/SPC TABLE 1108.1,
 1108.2.INCLUDE 1/2 AREA OF PARAPET WALLS
 PER SPC SEC.1108.3.
  
 8)SUBMIT CALCULATIONS FOR SECONDARY
 DRAINAGE.COMPLY W/SPC SEC.1109.2,1109.3,
 APPENDIX "A"& TABLE A101.2.
  
 9)CLEARLY SHOW DIMENSIONS OF OVERFLOW
 SCUPPER AND LOCATION OF SCUPPERS ON ROOF
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 10)SUBMIT A WATER RISER DIAGRAM FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 11)DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 12)2ND.FLOOR BATH SHALL BE FULLY ACCESS-
 IBLE PER FACBC 4.1.3(11).
  
 13)VERTICAL ACCESSIBILITY SHALL BE
 PROVIDED TO THE 2ND FLR.PER FACBC SEC.
 4.1.3.,FLA.STATUTE 553.509.
  
 14)A DRINKING FOUNTAIN IS REQD.ON THE
 2ND.FLOOR PER SPC TABLE 407.DRINKING
 FOUNTAIN SHALL COMPLY W/FACBC SEC.4.1.3
 (10)(A).
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.