| Plan Review Notes For Permit 00080584 |
| Permit Number |
00080584 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE PROVIDE BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH PANEL | | | SCHEDULES. | | | | | | 2)NOTE:PLEASE SEE RISER THIS SHOWS PANEL | | | "A" FEEDING PANEL "B" YET PANEL SCHEDULE | | | -S SHOW MDP FEEDING PANELS A&B ??? | | | PLEASE CLARIFY. | | | PLEASE SEE THAT YOU SHOW A 100A MAIN ON | | | RISER FUSED AT 100AMPS? YET YOU SHOW A | | | PANEL SCHEDULE?? PLEASE CLARIFY. | | | | | | 3)NOTE; PLEASE SEE PLAN PANEL"A" | | | DOESN'T SHOW FEEDING PANEL "B". | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|