Plan Review Notes
Plan Review Notes For Permit 00080578
Permit Number 00080578
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT THE PLANS ARE
 NOT SIGNED OR SEALED??? PLEASE SEE FL.
 STATE STATUES. 471.025 AND 61G15-23.002
  
 2)NOTE: PLEASE SEE FIRST TWO REVIEW
 NOTES. THEY BOTH NOTE NEC ARTS;210-52D
 AND 210-11-C-3 FOR DEDICATED BATH(S)
 MUST BE #12 AND 20AMP. YOU SHOW 15A AND
 #14 AWG. PLEASE CORRECT.
  
 3)NOTE: PLEASE NOTE THAT THE DRYER LOAD
 SHOWN EXCEEDS THE 80% OF BRKR RATING OF
 30A.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THE PLANS ARE BEING DENIED FOR
 NOT BEING SIGNED AND SEALED.PLEASE MAKE
 THE CORRECTIONS FOR THE OTHER TWO NOTES.
 NOTE #2 HAS BEEN GIVEN TWICE BEFORE.
 ONCE AGAIN IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372