| Plan Review Notes For Permit 00080578 |
| Permit Number |
00080578 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE ORIG NOTES. NOT ALL | | | NOTES WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT. MAIN DISCONNECTS/PANELS | | | ETC. 110-9 215-5 | | | | | | 3)NOTE: LIST REQ`D BATH(S) CIRCUIT(S) | | | PER 210-52D/210-11-C-3 | | | | | | | | | PLEASE SUBMIT THE ABOVE ON NEW REDRAWN | | | ELECTRICAL SHEET PER COUNTY/CITY WIDE | | | ADMINISTRATIVE CODE. 104.2.7 | | | | | | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULE "B" | | | AHU#3 SHOWN AT 7KW AND LOAD SHOWN AT | | | 10KW. PLEASE CORRELATE. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|