Plan Review Notes
Plan Review Notes For Permit 00080578
Permit Number 00080578
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ORIG NOTES. NOT ALL
 NOTES WERE ADDRESSED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. MAIN DISCONNECTS/PANELS
 ETC. 110-9 215-5
  
 3)NOTE: LIST REQ`D BATH(S) CIRCUIT(S)
 PER 210-52D/210-11-C-3
  
  
 PLEASE SUBMIT THE ABOVE ON NEW REDRAWN
 ELECTRICAL SHEET PER COUNTY/CITY WIDE
 ADMINISTRATIVE CODE. 104.2.7
  
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE "B"
 AHU#3 SHOWN AT 7KW AND LOAD SHOWN AT
 10KW. PLEASE CORRELATE.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372