| Date |
Text |
| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)DESIGN COMPLIANCE FORM MUST HAVE WET |
| | SIGNATURE OF ARCHITECT. |
| | |
| | 2)MEAN ROOF HEIGHT ON DESIGN COMPLIANCE |
| | FORM DIFFERS FROM 32'-6" SHOWN ON SHEET |
| | A-5 OF PLANS. PLEASE CORRECT. |
| | |
| | 3)PROVIDE INFORMATION FOR FOOTING AND |
| | COLUMN AT RIGHT SIDE OF GARAGE,SHEET A-2 |
| | |
| | 4)CLARIFY SIZE AND # OF REINFORCING |
| | STEEL IN THICKENED EDGE #1,SHEET A-2. |
| | |
| | 5)PROVIDE SOIL COMPACTION TEST AT FIRST |
| | INSPECTION. |
| | |
| | 6)CLARIFY TRUSS ANCHOR TYPES AND |
| | LOCATIONS AT LIBRARY AND MASTER BED ROOM |
| | AREA.SOME OF THESE ARE UNDISCERNIBLE.SEE |
| | SHEET A-8. |
| | |
| | 7)PLEASE CORRECT WALL SECTION 2 ON SHEET |
| | A-9 THE 12" DIMENSION AT THE FOOTING IS |
| | UNCLEAR. |
| | |
| | 8)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR ARCH |
| | WINDOWS. |
| | |
| | 9)PROVIDE CONSTRUCTION DETAIL FOR ARCH |
| | OPENINGS. |
| | |
| | 10)ALL NON-IMPACT RESISTANT GLAZING IS |
| | REQUIRED TO HAVE IMPACT PROTECTION. |
| | PROVIDE PRODUCT APPROVALS,KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR STORM PANELS |
| | OR APPLY UNDER A SEPARATE PERMIT. |
| | |
| | 11)PLEASE SPECIFY ON PLANS THE LOCATIONS |
| | OF GLAZINGS THAT ARE NOT IMPACT |
| | RESISTANT. |
| | |
| | 12)97 FL ACCESSIBILITY CODE SEC.4.22.2 |
| | REQUIRES A MINIMUM OF ONE ACCESSIBLE |
| | BATHROOM WITH A DOOR THAT HAS A 29" |
| | CLEAR OPENING.PLEASE INDICATE THE BATH- |
| | ROOM THAT MEETS THIS REQUIREMENT. |